Place of Origin: | Shenzhen, China |
---|---|
Brand Name: | Hongyan, HY |
Certification: | ISO, CCC, CE, RoHS. |
Model Number: | fire rated wire and cable |
Minimum Order Quantity: | 3000 Meter/Meters |
Price: | $0.30 - $0.50 / Meter |
Packaging Details: | 100 meters per roll, plastic reel, plywood drum, wooden pallet or others. |
Supply Ability: | 50000 Meter/Meters per Week |
Type: | Insulated | Application: | Industrial |
---|---|---|---|
Conductor Material: | Copper | Conductor Type: | Stranded |
Insulation Material: | Low Smoke Zero Halogen | Name: | 2h Fire Rated Cable, 2C X 1.5mm2, 450/750V, AS/NZS3013 & IEC60332 |
Conductor: | Stranded Annealed Copper, Class 2 | Fire Rated Material: | Mica Tape, Double Size |
Insulated Material: | Low Smoke, Zero Halogen | Voltage Rate: | 450/750V |
Operating Temperature: | -25°C -- +110°C | Colour: | Red Or White |
Min Bending Radius: | 10 X Cable's Diameter | Standard: | AS/NZS3013, IEC60332 |
Fire Rated Class: | WS52X | Port: | Shenzhen, China. |
High Light: | 2h fire rated cable,LSZH fire rated cable,IEC60332 LSZH Jacket Cables |
LSZH jacket Fire rated shield cable
--Products
***Core Number
two Cores, 2C.
***Cross Section
1.5 mm2
***Conductor
Stranded Annealed Copper, class 2, meet to IEC60228, AS/NZS1125, GB/T3953.
***Conductor Structuter
2C x 7/0.52 mm
***Fire Rated Material
MICA tape, IEC60332, GB/T19666, GA306.2.
***MICA Tape Date
Double size, widtch: 6mm x Thickness: 0.16mm.
***Insulation
Material: Fire Retardant, Low Smoking Zero Halogen, GB/T 19666, IEC60332.
Thickness: 0.7 mm
Colour: red, white
***Fire Rated Classification
WS5X, meet to AS/NZS 3013, IEC 60332.
***Innner Filler
Material: PET tape
Thickness: 0.0.05
Overlape Rate: ≥50%
***Inner Shield
Material: Tinned Copper Wire.
Structuter: 7/0.25mm
Cover Rate: ≥20%
***Out Shield
Material: Aluminium Foil
Specification: Thickness 0.17 x Width 6.0 mm
Cover Rate: 100%
Overlap Rate: ≥15%.
***Sheath
Material: Flame retardant, Low Smoking Zero Halogen.
Thickness: 1.2mm.
Colour: red or orange.
***Out Diameter
9.8-10.5 mm
***Voltage Rate
450/750V
***Refer Net Weight
150kgs/km
***Operating Temperature
-25°C to +110°C
***Min Bending Radius
10 x Cable Diameter
***Packing Model
100 meters per roll.
--Application
Hongyan Wire have been specifically designed for use with Australian or other marketing Fire Alarm and EWIS systems.
Hongyan fire rated cables have been independently tested and approved by EXOVA / Warrington Fire to the requirements of
AS/NZS 3013 for both fire and mechanical cable properties. All Hongyan Wires are certified 2 hour fire rated.
Hongyan Fire Rated Cables have also been tested and approved to electrical standards AS5000.2 and communication/wiring
standard AS/ACIF S008 by respective industry testing authorities.
The cable’s 7 stranded copper conductors and firm insulation material allows for neat placement on cable trays and allows ease of stripping and termination. When fixing fire rated cables to catenary wire our manufacturer’s recommendation is as follows:
If Cable bunch is >= 25mm diameter cables should be supported with Stainless Steel ties every 300mm
If Cable bunch is < 25mm diameter cables should be supported with Stainless Steel ties every 600mm.